Mithra · Engineering replay · Synthetic, indicative parameters
Can an AI load ride through a bad second on an islanded gas site?
A 2 × 1.5 MW lean-burn gas site carries 680 kW of priority AI load (256 GPUs plus cooling) and a 1.31 MW Bitcoin fleet as the swing load. Choose an event and a control architecture, then watch the bus frequency. On an island, a power shortfall appears as frequency within milliseconds, long before it would show up as missing kWh.
Bus frequency
Bus frequency57 Hz protection threshold59.3 Hz miner-feeder relay pickup
Power on the bus
Genset outputBattery (+ discharge)Miner drawAI + cooling served
Model and assumptions
Aggregate swing equation with per-unit isochronous PI governors. Engine power follows the governor through a 0.6 s lag, and increases are rate-limited to 25 %/s of rating. That is tuned so a 25 % load step dips the frequency about 6.6 % and recovers in about 5 s, and dropping 45 % of load overshoots about 6.3 %. Both are inside the range lean-burn gas gensets are specified for. Inertia is H = 1.0 s per genset, which is deliberately generous: real reciprocating sets are often lower, and that makes every result here worse. Loads are constant-power with no frequency damping. The battery is modelled as a grid-forming inverter with fast frequency droop (full output at 0.5 Hz, 30 ms response) and 1 MWh of usable energy. The bus is treated as lost below 54 Hz, or below 57 Hz for more than 2 s, or above 66 Hz. These are typical genset protection ranges, and real site settings vary.
| Architecture | Behaviour |
|---|---|
| Mithra today | The current open-source controller. It runs a 10 s loop, sheds one miner per loop below 59 Hz and all miners below 57.5 Hz. Commands land after the API latency. |
| Supervisory only | A 1 s loop that sheds the miner fleet to a target (85 % of online engine capacity minus maximum priority load) and restores at 50 kW per second while frequency is healthy. |
| Two-speed | An 81U under-frequency relay opens the miner feeder at 59.3 Hz (0.2 s clearing). Mithra then holds the miners asleep, recloses the feeder and restores to target. |
Not modelled: voltage and reactive power, governor load-sharing errors, GPU power-supply ride-through limits, fuel-system dynamics beyond the available-power cap, and network latency jitter. This is a synthetic comparison of architectures, not a calibrated plant study.